Field Cards
Thresholds
Thresholds — Field Card
Editions: 2024 IFC §510 + NFPA 1225-2022 Ch.18 + FCC §90.219. The fire code official can set the exact thresholds — confirm Savannah FMO numbers (
../OPEN-ITEMS.md). Numbers and section numbers are facts; this card paraphrases — no code text reproduced.
Core numbers
| What | Requirement | Cert | Where |
|---|---|---|---|
| Coverage — general area | signal in ≥ 95% of floor area, per floor | [Fact] |
NFPA 1225 §18; IFC §510 |
| Coverage — critical areas | signal in ≥ 99% of those areas | [Fact] |
NFPA 1225 §18; IFC §510 |
| Inbound signal (outside → in-building radio) | ≥ −95 dBm | [Fact]* |
NFPA 1225 §18 / NFPA 72 |
| Outbound signal (in-building → dispatch) | ≥ −95 dBm | [Fact]* |
NFPA 1225 §18 |
| Voice quality | ≥ DAQ 3.0 (or equivalent SINR) | [Fact] |
NFPA 1225 §18; IFC §510 |
| Donor ↔ indoor antenna isolation | ≥ system gain + 20 dB (no oscillation) | [Fact] |
NFPA 1225 §18 |
| Equipment listing | UL 2524 listed | [Fact] |
IFC §510; NFPA 1225 |
| Secondary (standby) power | required — 12 hr vs 24 hr | [Verify] |
OPEN-ITEMS |
* −95 dBm is the standard figure, but the code lets the fire code official set the exact level — confirm Savannah's number. [Verify]
Critical areas (the 99% list)
[Fact] Fire command center · fire pump rooms · interior exit stairways & exit passageways · elevator lobbies · standpipe cabinets · sprinkler sectional-valve locations · plus anything the fire code official designates.
Before you call pass/fail
- These are coverage / performance numbers only. Donor authorization (FCC §90.219 + licensee consent), monitoring/supervision, and survivable standby power are separate gates — see
passfail-card.md. - Anything not yet confirmed for Savannah is
[Verify]in../OPEN-ITEMS.md. Never present[Verify]as settled.
Sources: GA OCI – NFPA 1225 Ch.18 · UpCodes – IFC 510 ERCES · ICC – 2024 IFC §510
Pass / Fail
Pass/Fail Card — Field Card
Govern to 2024 IFC §510 + NFPA 1225-2022 Ch.18 + FCC §90.219. Confirm Savannah FMO specifics in
../OPEN-ITEMS.md. All gates must pass — coverage alone is not a pass.
A. Coverage / signal (numbers → thresholds.md)
- [ ] ≥95% of general floor area meets signal, per floor
[Fact] - [ ] ≥99% of critical areas meet signal
[Fact] - [ ] Inbound and outbound ≥ −95 dBm (or FMO-set level)
[Fact]* - [ ] Voice ≥ DAQ 3.0 (P25 equiv. ~SINR 18 dB / BER ≤2.5%)
[Fact] - [ ] Savannah grid: ≥20 grids/floor (20×20 ft; 40×40 if floor >32,000 sf); failed common-area grids within FMO limit
[Verify]
B. RF integrity
- [ ] Donor↔indoor isolation ≥ system gain + 20 dB; no oscillation
[Fact] - [ ] BDA has anti-oscillation + per-channel AGC
[Fact] - [ ] Uplink noise / emissions within FCC limits (no donor-site interference)
[Fact]
C. Authorization & equipment
- [ ] UL 2524-listed equipment
[Fact] - [ ] FCC §90.219 compliant + written licensee consent to retransmit (SEGARRN operator)
[Fact] - [ ] Class A (channelized) BDA per regional norm
[Verify] - [ ] Designer/lead tech: FCC GROL + training/mfr cert
[Verify]
D. Power, survivability, monitoring
- [ ] Secondary power present + supervised — duration per FMO (12 vs 24 hr)
[Verify] - [ ] 2-hour rated pathway / CI cable (UL 2196) where required
[Fact] - [ ] Trouble signals to FACP/attended location: AC loss, low battery, amp fail, antenna/donor fault, oscillation
[Fact] - [ ] NEMA-4/4X enclosure; signage/labeling; Knox/access switch
[Verify]
E. Paper
- [ ] Stamped design + as-built; grid datasheets per floor; cal certs (NIST ≤12 mo); FCC consent letter; UL listings
- [ ] Letter of Certification to FMO before CO; annual results → new Letter of Authorization
[Verify]
REJECT if any gate fails or any required doc is missing. Log [Verify] items not yet ruled on — don't pass on assumption.
* exact dBm can be FMO-set. Sources: GA OCI NFPA 1225 Ch.18 · UpCodes IFC 510 · eCFR 47 §90.219
Contacts
Contacts — Field Card
Numbers below are from official/public sources but change — confirm your direct FMO, radio-shop, and SEGARRN lines in person (see
../OPEN-ITEMS.md). Never act on an unconfirmed number for a licensee-consent or dispatch matter. Nothing here is fabricated; unknowns are marked[Verify].
Savannah (your office)
| Who | Contact | Cert |
|---|---|---|
| Savannah Fire Rescue (main) | 912-651-6756 · 121 E Oglethorpe Ave, Savannah 31401 | [Fact] |
| Fire Marshal's Office — direct line/email | via main line; no separate published number found | [Verify] |
| City Radio Shop / SEGARRN system manager (licensee consent, freqs, donor site) | not public — get from FMO day 1 | [Verify] |
County / region
| Who | Contact | Cert |
|---|---|---|
| Chatham County Fire (unincorporated) | (912) 219-0420 · 1249 Eisenhower Dr, Savannah 31406 | [Fact] |
| Chatham County (general / fire svcs) | (912) 652-7175 | [Fact] |
| Chatham 911 / Emergency Services | 911 (emergencies) · admin line [Verify] |
[Fact]/[Verify] |
State
| Who | Contact | Cert |
|---|---|---|
| GA Office of Insurance & Safety Fire Commissioner (OCI) | (404) 656-2070 · (800) 656-2298 | [Fact] |
| GA State Fire Marshal | (470) 572-5722 | [Fact] |
| GA DCA — Construction Codes | (404) 679-3118 · codes@dca.ga.gov | [Fact] |
First-day asks (fill these in)
- FMO plan-review contact + ERCES submittal/forms →
[Verify] - Who issues licensee written consent to retransmit on SEGARRN →
[Verify] - Radio-shop POC for donor-site coordination + acceptance-test witness →
[Verify]
Sources: Savannah Fire · Chatham Fire · GA OCI · ICC – Georgia
Frequencies
Frequencies — Field Card
Do not test, design, or pass against guessed frequencies. The exact channels/talkgroups are operational data from the system manager / city radio shop — get them in writing. Nothing here is invented; specifics are
[Verify].
The system
[Fact]The region runs on SEGARRN — Southeast Georgia Regional Radio Network, a P25 trunked public-safety system in the 700/800 MHz range serving Savannah/Chatham.[Verify]Control channels, talkgroups, donor-site frequencies, and call signs — not published on free public sources; obtain from the SEGARRN system manager / Savannah radio shop.
What the ERCES must do
[Fact]Cover all frequencies the AHJ assigns for the building (the responder radio set actually used), inbound and outbound.[Fact]Operating a BDA on these frequencies requires FCC §90.219 compliance + written consent from the SEGARRN licensee before it goes live — confirm the consent letter exists. (→fcc-spectrum.mdwhen built.)[Verify]Donor antenna must be aimed/optimized to the correct SEGARRN donor site — coordinate with the radio shop.
Get-it-in-writing checklist
- [ ] SEGARRN bands + specific channels/talkgroups for this building → from radio shop
[Verify] - [ ] Which agency/licensee holds the FCC license + who signs retransmit consent
[Verify] - [ ] Donor site + recommended donor-antenna aiming
[Verify] - [ ] The exact portable radio model/freqs to use for the talk-in/out acceptance test
[Verify]
Sources: RadioReference DB · eCFR 47 §90.219. SEGARRN specifics intentionally omitted until confirmed — see ../OPEN-ITEMS.md.
Forms
Master Inspection Checklist
Master Inspection Checklist
How to use: fill every
____and mark each item P / F / N/A. Record real numbers, not "ok". Anything that depends on an unconfirmed local rule is tagged[Verify]— note the FM's answer in the line. When done, save and upload this file and I'll analyze it (theRESULTSblock at the bottom is what I parse first). Govern to 2024 IFC §510 + NFPA 1225-2022 Ch.18 + NFPA 72/IFC §907 + FCC §90.219; confirm editions in../OPEN-ITEMS.md.
0. Header
- Date:
____Inspector:____Type: ☐ Plan review ☐ Acceptance ☐ Annual ☐ Re-test - Building / address:
____Permit #:____Occupancy / stories / sq ft:____ - Editions enforced today (from FMO): IFC
____· NFPA 1225____· NFPA 72____[Verify] - Systems present: ☐ ERCES/BDA ☐ Fire alarm ☐ Both
1. ERCES — applicability (IFC §510.1/.2)
- ☐ P ☐ F ☐ N/A — ERCES required? exterior/responder-radio coverage test result:
____dBm[Fact]510.1 - ☐ P ☐ F ☐ N/A — Construction + operational permits on file
[Fact]510.3
2. ERCES — signal & coverage (IFC §510.4.1 / NFPA 1225 §18.8–18.9)
Grid: ☐ 20×20 ft ☐ 40×40 ft (floor >32,000 sf) # grids/floor: ____ [Verify] Savannah spec
| Floor | # grids | # pass (≥ thr) | % pass | Critical-area % | Min dBm in | Min dBm out | DAQ |
|---|---|---|---|---|---|---|---|
| __ | __ | __ | __% | __% | __ | __ | __ |
| __ | __ | __ | __% | __% | __ | __ | __ |
- ☐ P ☐ F — General areas ≥95% meet signal [Fact] §18.8.4 / 510.4.1.3
- ☐ P ☐ F — Critical areas ≥99% [Fact] §18.8.3
- ☐ P ☐ F — Inbound & outbound ≥ −95 dBm (or FMO level ____) [Fact] 510.4.1.1/.2
- ☐ P ☐ F — Voice ≥ DAQ 3.0* (P25 ~SINR 18 dB / BER ≤2.5%) [Fact] §18.8.2
- ☐ P ☐ F — Failed common-area grids within FMO limit (max ____) [Verify]
3. ERCES — RF integrity (NFPA 1225 §18.3)
- ☐ P ☐ F — Donor↔indoor isolation ≥ system gain + 20 dB; measured: gain
__dB, isolation__dB[Fact]§18.3.2 - ☐ P ☐ F — No oscillation; anti-oscillation + per-channel AGC present
[Fact]510.4.2.4 - ☐ P ☐ F — Uplink noise / emissions within FCC limits; no donor-site interference
[Fact]§18.6 - ☐ P ☐ F — Near-far / antenna density addressed
[Fact]510.4.2.8 / §18.3.4
4. ERCES — equipment & authorization
- ☐ P ☐ F — Equipment UL 2524 listed (models:
____)[Fact]§18.12 - ☐ P ☐ F — FCC §90.219 compliant + written licensee consent to retransmit on file
[Fact]510.5.5 / §18.7.2 - ☐ P ☐ F — Class A (channelized) BDA
[Verify]· donor antenna gain__dBi (cap____)[Verify] - ☐ P ☐ F — Designer/lead tech FCC GROL + training/mfr cert
[Verify]510.5.3
5. ERCES — power, survivability, monitoring (IFC §510.4.2 / NFPA 1225 §18 / NFPA 72)
- ☐ P ☐ F — Secondary power present + supervised; duration
____hr (FMO req__hr)[Verify] - ☐ P ☐ F — Standby load test result:
____[Fact] - ☐ P ☐ F — 2-hr rated pathway / CI cable (UL 2196) where required
[Fact] - ☐ P ☐ F — Trouble signals to FACP/attended: ☐AC loss ☐low batt ☐charger ☐amp fail ☐antenna ☐donor ☐oscillation
[Fact]510.4.2.5 - ☐ P ☐ F — NEMA-4/4X enclosure · signage/labeling · Knox/access switch
[Verify]
6. Fire alarm (NFPA 72 / IFC §907)
- ☐ P ☐ F ☐ N/A — FA system required & provided per §907
[Fact] - ☐ P ☐ F — Secondary power 24 hr (or 8 hr w/ approved risk analysis)
[Fact] - ☐ P ☐ F — Record of Completion + inspection/testing form executed
[Fact] - ☐ P ☐ F — Off-premises monitoring (alarm/supervisory/trouble distinct)
[Fact] - ☐ P ☐ F — Devices tested: ☐control unit ☐annunciators ☐initiating ☐notification (audible/visible) ☐HVAC shutdown ☐elevator recall ☐door release
- ☐ P ☐ F — Exact NFPA 72 ITM cadence/sections verified vs adopted edition
[Verify]
7. ERCES ↔ fire-alarm interface
- ☐ P ☐ F — ERCES faults supervised by / annunciated through the FA system (where required)
[Fact] - ☐ P ☐ F — ERCES trouble at building FACP vs separate annunciator
[Verify]
8. Documentation
- ☐ stamped design + as-built ☐ grid datasheets/floor ☐ cal certs (NIST ≤12 mo, date
__) - ☐ FCC licensee consent letter ☐ UL 2524 listings ☐ FA Record of Completion
- ☐ ERCES Letter of Certification (acceptance) / annual Letter of Authorization
[Verify]
RESULTS (machine-parsed on upload — keep these keys)
building: ____
date: ____
type: ____ # plan-review | acceptance | annual | re-test
editions: IFC=____ NFPA1225=____ NFPA72=____
erces_coverage_general_pct: ____
erces_coverage_critical_pct: ____
erces_min_inbound_dBm: ____
erces_min_outbound_dBm: ____
erces_daq: ____
erces_isolation_margin_dB: ____
erces_standby_hours: ____
fire_alarm_present: yes/no
fire_alarm_secondary_hours: ____
licensee_consent_on_file: yes/no
ul2524_listed: yes/no
overall: PASS / FAIL / CONDITIONAL
fail_items: [ ____ ] # list the failed line(s)
verify_open: [ ____ ] # [Verify] items not yet ruled by FMO
violations_cited: [ §____ : ____ ]
notes: ____
* −95 dBm is the standard; the fire code official can set the level — confirm. See ../10-code/citation-map.md for every §, ../OPEN-ITEMS.md for unresolved local rules.
Field-Test Datasheet
Field-Test Datasheet — Floor ____
Building: ____ Date: ____ Tech: ____ Radio (model/agency): ____
Instrument + cal cert #/date (NIST ≤12 mo): ____ Editions: IFC ____ / 1225 ____
Grid size: ☐ 20×20 ft ☐ 40×40 ft Required level: ____ dBm DAQ min: 3.0
| Grid # | Location | Critical? | Inbound dBm | Outbound dBm | DAQ | P/F |
|---|---|---|---|---|---|---|
| 1 | ____ |
☐ | ____ |
____ |
____ |
☐ |
| 2 | ____ |
☐ | ____ |
____ |
____ |
☐ |
| 3 | ____ |
☐ | ____ |
____ |
____ |
☐ |
| … |
Totals — General: __/__ = __% (need ≥95%) · Critical: __/__ = __% (need ≥99%)
Isolation: gain __ dB / isolation __ dB (need ≥ gain+20) · Oscillation: ☐none
Standby test: ____ · Faults annunciated at FACP: ☐AC ☐batt ☐amp ☐antenna ☐donor ☐osc
Floor result: ☐ PASS ☐ FAIL Notes: ____
Plan-Review Checklist
Plan-Review Checklist (printable)
Project: ____ Permit #: ____ Reviewer: ____ Date: ____
| # | Item | Rule | OK | N/A |
|---|---|---|---|---|
| 1 | Stamped design (GA PE [Verify]) + designer FCC GROL/cert |
510.5.3 | ☐ | ☐ |
| 2 | RF design + link budget | §18.9 | ☐ | ☐ |
| 3 | Floor plans: antenna layout + grid; critical areas marked | §18.8.3/.4 | ☐ | ☐ |
| 4 | Standby-power calc (hrs [Verify]) |
510.4.2.3 | ☐ | ☐ |
| 5 | Cut sheets — UL 2524; BDA Class A [Verify] |
§18.12 | ☐ | ☐ |
| 6 | Donor antenna type/gain/aim | 510.5.1 | ☐ | ☐ |
| 7 | Isolation ≥ gain + 20 dB shown | §18.3.2 | ☐ | ☐ |
| 8 | FCC §90.219 + written licensee consent | 510.5.5/§18.7.2 | ☐ | ☐ |
| 9 | Monitoring points + FACP annunciation | 510.4.2.5 | ☐ | ☐ |
| 10 | 2-hr pathway where required | — | ☐ | ☐ |
| 11 | Enclosure/signage/Knox | [Verify] |
☐ | ☐ |
Disposition: ☐ Approved ☐ Approved w/ comments ☐ Rejected Reviewer sign: ____
Inspection Report
Inspection Report
Building / address: ____ Permit #: ____ Occupancy: ____
Date: ____ Inspector: ____ Type: ☐Plan review ☐Acceptance ☐Annual ☐Re-test
Editions enforced: IFC ____ / NFPA 1225 ____ / NFPA 72 ____
Systems
- ERCES: ☐ Pass ☐ Fail ☐ N/A Fire alarm: ☐ Pass ☐ Fail ☐ N/A Interface: ☐ Pass ☐ Fail
Key results
Coverage gen/crit: __% / __% · min in/out dBm: __ / __ · DAQ: __ · isolation margin: __ dB
ERCES standby: __ hr · FA standby: __ hr · licensee consent on file: ☐yes ☐no · UL 2524: ☐yes ☐no
Findings / violations (cite §)
____— §________— §____
Disposition
☐ Approved / Letter of Certification (or Authorization) issued
☐ Conditional — items due by ____
☐ Rejected — NOV issued (notice-of-violation.md)
Open [Verify] carried: ____ Inspector sign: ____
Notice of Violation
Notice of Violation
To (owner/agent): ____ Building / address: ____ Permit #: ____
Issued by: ____ Date: ____ NOV #: ____
| # | Violation (plain language) | Code citation | Correction required | Due |
|---|---|---|---|---|
| 1 | ____ |
§____ |
____ |
____ |
| 2 | ____ |
§____ |
____ |
____ |
Re-inspection: ☐ required on/after ____ Penalty for non-compliance: ____ [Verify]
Not a legal determination — issued under the authority of the Fire Marshal / AHJ. Inspector sign:
____Received by:____
Code
Citation Map
Citation Map
IFC §510 outline verified on UpCodes; NFPA 1225 Ch.18 numbers verified from the GA OCI copy. Which edition Savannah enforces is
[Verify](P0 in../OPEN-ITEMS.md) — that decides which §s actually bind. No code text reproduced; numbers/§s are facts.
ERCES — requirement → citation
| Requirement | 2024 IFC §510 | NFPA 1225-2022 Ch.18 | Cert |
|---|---|---|---|
| Required — new buildings | 510.1 | — | [Fact] |
| Required — existing buildings | 510.2 | — | [Fact] |
| Permits (constr. + operational) | 510.3 / .3.1 / .3.2 | 18.7 Approval & Permit; 18.7.1 Plans | [Fact] |
| Min signal into building (inbound/downlink) | 510.4.1.1 | 18.9.1 Downlink | [Fact] |
| Min signal out of building (outbound/uplink) | 510.4.1.2 | 18.9.2 Uplink | [Fact] |
| System performance / DAQ | 510.4.1.3 | 18.8.2 (max acceptable / quality) | [Fact] |
| Coverage — general areas (95%) | 510.4.1.3 | 18.8.4 General building areas | [Fact] |
| Coverage — critical areas (99%) | 510.4.1.3 | 18.8.3 Critical areas | [Fact] |
| Amplifiers / components | 510.4.2.1 | 18.12 System Components | [Fact] |
| Oscillation detection/control + isolation | 510.4.2.4 | 18.3.2 (oscillation) | [Fact] |
| Standby power | 510.4.2.3 | 18.3.1 Enclosures/battery power | [Fact] |
| System monitoring / supervisory signals | 510.4.2.5 / .5.1 | within Ch.18 | [Fact]/[Inference] |
| Added / changed frequencies | 510.4.2.6 | 18.11 / 18.11.1 / 18.11.2 | [Fact] |
| Design documents / plans | 510.4.2.7 | 18.7.1 Plans | [Fact] |
| Near-far effect / antenna density | 510.4.2.8 | 18.3.4 Communication Antenna Density | [Fact] |
| Noise / non-interference | 510.4.2.9 | 18.6 Non-Interference; 18.9.3 noise floor | [Fact] |
| Donor antenna mounting/coax/grounding | 510.5.1 | 18.3.3 Mounting; 18.4.x coax/discharge; 18.10 Donor Antenna | [Fact] |
| Approval prior to install | 510.5.2 / .5.2.1 | 18.2 Approval | [Fact] |
| Personnel qualifications (FCC GROL + cert) | 510.5.3 | 18.2.2 (qualified designer) | [Fact] |
| Acceptance test procedure | 510.5.4 | 18.5 Testing Requirements | [Fact] |
| FCC compliance + licensee written consent | 510.5.5 | 18.7.2 Written consent from RF licensee | [Fact] |
| Maintenance / annual | 510.6 | 18.5 Testing & maintenance | [Fact] |
| Equipment listed to UL 2524 | 510.4.2 components | 18.12.1.x (listed RF devices/repeaters) | [Fact] |
| FCC signal-booster rules | — | — → 47 CFR §90.219 | [Fact] |
Fire-alarm interface (you inspect this alongside the FA system)
| Requirement | Where | Cert |
|---|---|---|
| ERCES trouble/supervisory signals annunciated at the FACP / constantly-attended location | NFPA 72 (monitoring of integrity) + IFC 510.4.2.5 | [Fact]/[Verify] § |
| Fire-alarm systems — installation/where required | IFC §907; NFPA 72 | [Fact] |
| Monitored faults: AC loss, low/depleted battery, charger fail, amp/booster fail, antenna & donor disconnect, oscillation | IFC 510.4.2.5; NFPA 72 supervision | [Fact] |
| Secondary power / 2-hr survivable pathway for the alarm + ERCES circuits | NFPA 72; IFC §510 / §907 | [Fact]/[Verify] |
| Adopted NFPA 72 edition (drives the above specifics) | — | [Verify] (P0) |
NFPA 72 section-level pinpoints are
[Verify]until the adopted NFPA 72 edition is confirmed and checked on the free portal — seefire-alarm-and-erces.mdand../OPEN-ITEMS.md.
Sources: UpCodes IFC 510 · GA OCI NFPA 1225 Ch.18 · eCFR 47 §90.219
Code Stack
Code Stack
Which edition Georgia/Savannah enforces is
[Verify](P0 in../OPEN-ITEMS.md). Govern to: 2024 IFC + NFPA 1225-2022 Ch.18 + NFPA 72 + UL 2524 + FCC 47 CFR Part 90.
The documents
| Document | Role | Key location | Cert |
|---|---|---|---|
| 2024 IFC §510 | When an ERCES is required + the building-code technical hooks; defers detail to NFPA 1225 | IFC Ch.5 §510 | [Fact] |
| 2024 IFC §907 (Ch.9) | Where fire alarm & detection systems are required + commissioning | IFC Ch.9 §907 | [Fact] |
| NFPA 1225-2022 Ch.18 | The ERCES technical standard — coverage, signal, isolation, donor, testing, components, licensee consent | Ch.18 (§18.1–18.12) | [Fact] |
| NFPA 72 | National Fire Alarm & Signaling Code — fire-alarm install/test/maint and supervision/monitoring of the ERCES | NFPA 72 (Ch. on ITM + supervising station) | [Fact]/[Verify] ed. |
| UL 2524 | Product listing standard for in-building 2-way ERCES equipment | UL 2524 | [Fact] |
| FCC 47 CFR Part 90 (§90.219) | Signal-booster rules + licensee written consent to retransmit on public-safety LMR | eCFR Title 47 §90.219 | [Fact] |
How the pieces fit
- IFC says whether you need an ERCES (§510) and a fire-alarm system (§907); NFPA 1225 Ch.18 says how the ERCES must perform; NFPA 72 governs the fire-alarm system and the supervision of the ERCES (faults annunciate at the FACP); UL 2524 is what the equipment must be listed to; FCC Part 90 controls the RF (you cannot energize a BDA without the licensee's written consent — IFC 510.5.5 / NFPA 1225 §18.7.2).
- Fire-alarm tie-in (for joint inspections): the ERCES is a monitored, supervised system off the fire-alarm infrastructure. Fire-alarm secondary power = 24 hr (NFPA 72; or 8 hr with AHJ-approved risk analysis) — note this is a separate number from the ERCES standby-power question. See
fire-alarm-and-erces.md.
Georgia adoption tracks (who adopts what)
[Fact]GA Safety Fire Commissioner / OCI adopts and amends the IFC for fire-safety enforcement — this is the version that binds the fire inspector, not DCA's base text.[Fact]GA DCA (Construction Codes) maintains the base I-Codes (building track).[Fact]2024 IFC is the Georgia statewide edition, effective 2026-01-01.[Verify]Which NFPA 1225 edition (2022 vs 2025) and NFPA 72 edition Georgia/Savannah reference, and any City of Savannah local amendments to §510. → P0 in../OPEN-ITEMS.md.
Sources: UpCodes IFC 510 · GA OCI NFPA 1225 Ch.18 · eCFR 47 §90.219 · ICC – Georgia
Edition Deltas
Edition Deltas
Why this file exists: the City of Savannah's published BDA/ERRCS guide is 2018-IFC-based, while Georgia's statewide edition is 2024 IFC (eff. 2026-01-01). Know the gap so you don't cite a superseded rule.
IFC 2018 → 2024 §510
[Fact]Rename: "Emergency Responder Radio Coverage (ERRC)" → "Emergency Responder Communication Enhancement System (ERCES)." Same system, new term — match the submittal's vocabulary to the edition in force.[Fact]Defers technical detail to NFPA 1225. The 2024 §510 leans on NFPA 1225 Ch.18 for the performance/technical specs rather than spelling them all out in the IFC.[Fact]Restructured subsections (verified outline): 510.1 new / 510.2 existing / 510.3 permits / 510.4 technical (signal, system design, standby, monitoring, near-far, noise) / 510.5 installation (donor mounting, approval, personnel quals, acceptance test, FCC compliance) / 510.6 maintenance.[Inference]Net effect: stronger emphasis on monitoring/supervision, documentation, personnel qualifications, and FCC/licensee consent vs the 2018 text.
NFPA 1221 → NFPA 1225
[Fact]NFPA 1225-2022 consolidated and superseded NFPA 1221 (emergency services comms). ERCES radio-coverage requirements now live in NFPA 1225 Chapter 18. Older references to "NFPA 1221" point to the predecessor.[Verify]Whether GA/Savannah references NFPA 1225-2022 or -2025 (2025 strengthens the fire-alarm supervision interface). → P0 in../OPEN-ITEMS.md.
Isolation requirement history
[Fact]The donor↔indoor isolation margin was raised to ≥ system gain + 20 dB (up from a prior +15 dB) to keep margin as buildings/RF change post-install. Use +20 dB.
The practical rule
- When a submittal or the city guide cites a 2018 number, map it to the in-force edition before you accept or cite it. If the in-force edition isn't confirmed, treat the citation as
[Verify]and log it.
Sources: UpCodes IFC 510 · GA OCI NFPA 1225 Ch.18
Fire Alarm + ERCES
Fire Alarm & the ERCES Interface
Govern to NFPA 72 + IFC §907, plus IFC §510 / NFPA 1225 §18 for the ERCES tie-in. Adopted NFPA 72 edition is
[Verify](P0) — it sets the exact sections. No code text reproduced.
Fire-alarm essentials (NFPA 72 / IFC §907)
[Fact]Where required: IFC §907 lists the occupancies/conditions that mandate a fire-alarm & detection system.[Fact]Secondary (standby) power: 24 hr standby, then alarm load (commonly 5 min) — or 8 hr only with an AHJ-approved risk analysis. (This is the FA number; the ERCES standby duration is a separate[Verify]item.)[Fact]Acceptance package: executed NFPA 72 Record of Completion, the inspection & testing form, and the supervising-station / monitoring agreement before acceptance.[Fact]Monitoring: alarm, supervisory, and trouble must be distinct signals; off-premises monitoring via a listed supervising station (24-hr).[Fact]What gets tested: control unit, secondary power/batteries, remote annunciators, initiating devices, notification appliances (audible/visible), and interfaced functions (e.g., HVAC shutdown, elevator recall, door release).[Verify]Exact NFPA 72 chapter/section pinpoints (ITM cadence, ECS provisions) — confirm against the adopted edition on the free portal.
How the ERCES rides on the fire alarm
[Fact]The ERCES is a monitored, supervised system. These faults must annunciate at the FACP / constantly-attended location: AC power loss, low/depleted battery, charger failure, signal-booster/amplifier failure, antenna malfunction, donor-antenna disconnect, and oscillation (IFC 510.4.2.5; NFPA 1225 §18; NFPA 72 supervision).[Fact]Survivability: ERCES (and FA) circuits requiring it use a 2-hour rated pathway / CI cable (UL 2196).[Verify]Whether Savannah requires ERCES trouble at the building FACP specifically vs a separate annunciator, and the ERCES standby duration (12 vs 24 hr). →../OPEN-ITEMS.md.
Joint-inspection quick logic
- FA system itself compliant (NFPA 72 / §907) → see the FA section of the master checklist.
- ERCES present where required (§510) and its faults supervised by / annunciated through the FA system.
- Both have compliant secondary power (FA 24 hr; ERCES per FMO) and survivable pathways.
- Paperwork: FA Record of Completion and ERCES Letter of Certification/Authorization.
Sources: NFPA 72 · UpCodes IFC 510 · Portland FA acceptance checklist (reference)
Operations
When Required
When Required
Editions enforced are
[Verify](P0,../OPEN-ITEMS.md). Numbers/§s are facts; paraphrased.
The trigger
[Fact]An ERCES is required when in-building responder-radio coverage fails the minimum — i.e., the building can't meet the signal/coverage thresholds (../00-quickref/thresholds.md) on its own. Demonstrated by a radio coverage test. (IFC §510.1 new; §510.2 existing; NFPA 1225 §18.8.)[Fact]New buildings: §510.1. Existing buildings: §510.2 (typically on change of use / major reno, or when found deficient).
Exemptions (confirm exact figures locally)
[Verify]Small-building exemptions exist (commonly tied to stories / floor area / no below-grade floors), but the exact cutoffs are edition/AHJ-specific — confirm Savannah's numbers before exempting anything. Do not quote an exemption threshold from memory.[Inference]Where adequate coverage is already demonstrated by test, no system is required — but get the passing test documented and accepted by the FMO.
Inspector logic
- Coverage test at the building → meets thresholds? No system needed (document it).
- Fails → ERCES required (§510.1/.2). Move to plan review (
../30-plan-review/). - Existing building deficient on a periodic/triggered test → §510.2 path.
Sources: UpCodes IFC 510 · GA OCI NFPA 1225 Ch.18
Submittal Checklist
Plan-Review Submittal Checklist
Reject incomplete submittals. Each item cites where it's required.
[Verify]= confirm Savannah's exact form/threshold.
- [ ] Stamped design — signed/sealed by a GA-licensed PE (or FMO-accepted designer)
[Verify](confirm GA PE-stamp requirement) · designer FCC GROL + training/mfr cert (IFC 510.5.3)[Fact] - [ ] RF design + link budget — gain, losses, donor signal, predicted in-building levels (NFPA 1225 §18.9)
[Fact] - [ ] Coverage plan — floor plans showing antenna layout + the grid to be tested; general vs critical areas marked (§18.8.3/.4)
[Fact] - [ ] Standby-power calc — battery sizing for required duration (12 vs 24 hr
[Verify]) + alarm load (IFC 510.4.2.3)[Fact]/[Verify] - [ ] Equipment cut sheets — all RF devices UL 2524 listed; BDA class (expect Class A)
[Fact]/[Verify] - [ ] Donor antenna — type, gain (cap
[Verify]), mounting/aiming to the SEGARRN site (510.5.1; §18.3.3/18.10)[Fact] - [ ] Isolation — design shows donor↔indoor isolation ≥ system gain + 20 dB (§18.3.2)
[Fact] - [ ] FCC — §90.219 compliance + written licensee consent to retransmit (510.5.5 / §18.7.2)
[Fact] - [ ] Monitoring/supervision — fault points + annunciation at FACP/attended location (510.4.2.5)
[Fact] - [ ] Survivability — 2-hr pathway / CI cable where required
[Fact] - [ ] Enclosure/signage — NEMA-4/4X, labeling, Knox/access
[Verify]
See
red-flags.mdfor the defects these catch, and../10-code/citation-map.mdfor every §.
Red Flags
Plan-Review Red Flags
| Red flag | Why it fails | Rule |
|---|---|---|
| No FCC licensee consent letter | Can't legally retransmit on SEGARRN | 510.5.5 / §18.7.2 [Fact] |
| Class B (broadband) where Class A expected | Interference risk; regional norm is channelized | [Verify] (confirm Savannah) |
| Isolation < system gain + 20 dB | Oscillation / donor-site interference | §18.3.2 [Fact] |
| System gain > ~75 dB / no AGC | Pushes AGC/OLC, noise rise | [Inference] |
| No standby-power calc or wrong hours | Won't survive outage | 510.4.2.3 + [Verify] hrs |
| No 2-hr pathway where required | Loses comms in fire | [Fact] |
| Equipment not UL 2524 listed | Not code-listed | 510.4.2 / §18.12 [Fact] |
| Missing monitoring points / FACP annunciation | Faults go unnoticed | 510.4.2.5 [Fact] |
| Donor antenna gain excessive / wrong aim | Overload, near-far, interference | §18.3.3 + [Verify] cap |
| Citations to 2018 IFC / NFPA 1221 | Superseded edition | see ../10-code/edition-deltas.md |
| No critical-area designation on plans | Can't verify 99% | §18.8.3 [Fact] |
Acceptance Procedure
Acceptance Test Procedure
Govern to NFPA 1225 §18.5 + IFC 510.5.4. Confirm Savannah specifics (
../OPEN-ITEMS.md). Use the datasheet in../templates/field-test-datasheet.md; decide with../00-quickref/passfail-card.md.
Before you start
[Fact]FCC licensee consent on file; system energized legally.[Fact]Test gear NIST-cal ≤12 mo (equipment-and-cal.md); portable radio matches the responding agency's.- Confirm editions enforced + the FMO signal level (−95 dBm default)
[Verify].
Test
[Fact]Talk-out (uplink): from inside each grid, key to dispatch/base; confirm reception + voice quality.[Fact]Talk-in (downlink): from outside/base to the in-building portable; confirm.[Fact]Grid walk (grid-method.md): measure inbound & outbound dBm and DAQ at each grid center; record all (not just pass/fail).[Fact]Isolation test: verify donor↔indoor ≥ gain + 20 dB; no oscillation (§18.3.2).[Fact]Monitoring test: trip each fault (AC loss, low batt, amp/antenna/donor, oscillation) → confirm annunciation at FACP/attended (510.4.2.5).[Fact]/[Verify]Standby-power test: run on secondary power; confirm duration (12/24 hr per FMO).
Pass / paper
- Pass = ≥95% general / ≥99% critical grids meet level + DAQ, AND all gates above (
passfail-card.md). [Verify]Submit Letter of Certification + grid datasheets to FMO before CO.
Sources: GA OCI NFPA 1225 Ch.18 · UpCodes IFC 510
Grid Method
Grid Method
NFPA 1225 §18.8 coverage; Savannah grid specifics
[Verify]against the City BDA doc.
The method
[Fact]Divide each floor into an approximately uniform grid; measure at the center of each grid square.[Verify]Savannah: ≥ 20 grids per floor, squares 20×20 ft; floors > 32,000 sf may use 40×40 ft. Confirm against the current City BDA doc.[Fact]Record inbound & outbound dBm and DAQ at each square.
Pass criteria
[Fact]General areas: ≥ 95% of grids meet the level (−95 dBm or FMO level) + DAQ ≥ 3.0.[Fact]Critical areas: ≥ 99% of grids.[Verify]Savannah may cap how many failed grids are allowed in common areas (e.g., "no more than N") — confirm.
Worked example (20-grid floor)
- General floor, 20 grids. Results: 19 grids ≥ −95 dBm, 1 grid at −98 dBm.
- 19/20 = 95% → PASS (meets ≥95%), if the 1 failing grid is within the FMO's allowed-failures rule
[Verify]. - Same floor's critical area = 5 grids (stair + elevator lobby + pump room). Results: 5/5 ≥ −95 dBm = 100% → PASS (needs ≥99%, i.e., effectively all).
- Flip it: if 2 of 20 general grids fail → 18/20 = 90% → FAIL (below 95%); re-engineer coverage.
Numbers are illustrative of the math, not Savannah-confirmed thresholds. Confirm the level + failed-grid rule (
../OPEN-ITEMS.md).
Sources: GA OCI NFPA 1225 Ch.18 · Savannah Fire
Test Equipment & Cal
Test Equipment & Calibration
[Fact]Instrument: P25-capable service monitor or spectrum analyzer covering 700/800 MHz + P25; able to read signal power (dBm) and demodulate for DAQ/BER.[Fact]Calibration: NIST-traceable, ≤ 12 months; verify the cal date/cert before testing — expired cal invalidates the test.[Fact]Settings (typical): RBW ~10 kHz for narrowband PS signals; VBW ~⅓ RBW; enable preamp for weak signals; Max-Hold to catch variation.[Fact]DAQ: P25 equivalent ≈ SINR ≥ 18 dB / BER ≤ 2.5% for DAQ 3.0.[Fact]Talk radio: use a calibrated portable matching the responding agency's current model/freqs (coordinate with the radio shop[Verify]).[Inference]Capture screenshots/logs per grid for the report.
Sources: Anritsu — ERCES test solution
BDA / DAS / Donor
BDA / DAS / Donor Antenna
Pieces
[Fact]BDA (bi-directional amplifier): captures the outdoor donor signal, amplifies, redistributes indoors via the DAS (distributed antennas); amplifies both directions.[Fact]Donor antenna: directional antenna aimed at the SEGARRN site; provides isolation + the outside link.
Class A vs Class B (FCC §90.219)
[Fact]Class A = channelized (narrow passband, ~≤ 75 kHz): amplifies only the assigned channels; filters the rest. Preferred/expected for public safety.[Fact]Class B = broadband (passband > 75 kHz): amplifies the whole band indiscriminately; higher interference risk; FCC registration.[Verify]Confirm Savannah requires Class A.
RF gotchas (acceptance failures)
[Fact]Isolation ≥ system gain + 20 dB (donor↔indoor). Under it → oscillation (BDA amplifies its own re-radiation → saturation, noise rise at the donor site).[Fact]Desensitization: BDA uplink noise raises the base-station noise floor → shrinks the public-safety coverage. Keep uplink noise/emissions within FCC limits.[Inference]Typical system gain ~60–75 dB; high gain w/o margin trips AGC/OLC. FCC output power capped (≈ 5 W) per §90.219.
Sources: eCFR 47 §90.219 · GA OCI NFPA 1225 Ch.18
Power & Survivability
Power & Survivability
Standby power
[Fact]Secondary power required, supervised (IFC 510.4.2.3; NFPA 1225 §18).[Verify]Duration: 12 hr vs 24 hr. IFC/NFPA baseline is commonly 12 hr; many AHJs amend to 24 hr. Confirm Savannah (P0). (Note: the fire-alarm system's secondary power is 24 hr — different number; see../10-code/fire-alarm-and-erces.md.)[Inference]Battery or generator-backed; if battery, sized for the full duration at 100% system load.
Worked battery-sizing example (illustrative)
- Suppose system draws 3.0 A at 24 VDC standby. For a 24 hr requirement:
- Energy = 3.0 A × 24 h = 72 Ah before deratings.
- Add temperature/age derating (~20–25%) → size ≈ 72 / 0.8 ≈ 90 Ah.
- For a 12 hr requirement → ≈ 45 Ah derated.
[Verify]Use the actual standby + alarm load from the cut sheets and the FMO's hours; confirm the load test (commonly a timed run on secondary power).
Survivability
[Fact]Where required, 2-hour fire-rated pathway / CI cable (UL 2196) for the ERCES (and interfaced FA) circuits.[Verify]Which pathways Savannah requires rated (everywhere vs conditioned).
Sources: UpCodes IFC 510 · GA OCI NFPA 1225 Ch.18
Monitoring & Supervision
Monitoring & Supervision
IFC 510.4.2.5; ties to the fire alarm (NFPA 72) — see
../10-code/fire-alarm-and-erces.md.
Required fault/trouble signals
[Fact]AC power loss to the ERCES[Fact]Low / depleted battery and charger failure[Fact]Signal-booster / amplifier failure[Fact]Antenna malfunction and donor-antenna disconnect[Fact]Oscillation detected[Fact]All annunciate at the FACP / constantly-attended location; distinct from alarm signals.
Physical
[Verify]NEMA-4 / 4X enclosure where the environment requires.[Verify]Signage / labeling (RF, system ID, disconnect) per FMO.[Verify]Knox box / access switch location + posted operation.
Inspector test
- Trip each fault above → confirm it reports correctly (part of acceptance + annual).
Sources: UpCodes IFC 510
FCC & Spectrum
FCC & Spectrum
The legal gate. No consent = the BDA cannot operate, regardless of RF performance.
[Fact]47 CFR §90.219 governs signal boosters on Part 90 (public-safety LMR) frequencies. Class A (channelized) vs Class B (broadband).[Fact]Written consent from the FCC licensee (the agency/operator that holds the SEGARRN license) is required before a booster operates on their frequencies. (Mirrored in IFC 510.5.5 / NFPA 1225 §18.7.2.)[Fact]Equipment must hold FCC equipment authorization / type acceptance.[Fact]Booster must not cause harmful interference; operator must cease/correct on demand; emissions limited.[Verify]Who at the SEGARRN operator / city radio shop signs the consent, and the form. →../OPEN-ITEMS.mdP3.
Sources: eCFR 47 §90.219 · GA OCI NFPA 1225 Ch.18
Annual Test
Annual Test & Maintenance
IFC 510.6; NFPA 1225 §18.5. Confirm Savannah's annual process (
../OPEN-ITEMS.md).
Cadence
[Fact]Annual test/inspection, and whenever structural/material changes could affect coverage (additions, remodels, new adjacent construction blocking the donor).[Inference]No fixed "5-year reacceptance" in NFPA 1225 Ch.18 — treat any 5-yr figure as jurisdiction-specific[Verify].
Scope
[Fact]Grid re-test (signal/DAQ across floors + critical areas) —40-field-test/grid-method.md.[Fact]Hardware inspection: donor + DAS antennas, BDA, cabling for damage.[Fact]Battery / standby performance (timed load test).[Fact]Fault/monitoring test (all points report to FACP).[Fact]Gain/baseline comparison vs the acceptance baseline.
Baseline & disposition
[Verify]Deviation that forces re-commissioning (e.g., > 3 dB drop vs baseline) — confirm Savannah's threshold.[Verify]Annual results submitted to FMO → new Letter of Authorization (valid ~1 yr). Confirm form/timeline.
Sources: UpCodes IFC 510 · GA OCI NFPA 1225 Ch.18
Reference
Decision Trees
Decision Trees
- Coverage test at building? Meets thresholds → no system required (document). Fails → ERCES required (§510.1 new / §510.2 existing).
- No written FCC licensee consent? → Stop. Cannot energize/accept regardless of RF (510.5.5 / §18.7.2).
- Isolation < system gain + 20 dB / oscillation present? → Fail; re-engineer (more separation, directional donor, lower gain) before acceptance (§18.3.2).
- One general grid fails (e.g., 19/20)? → 95% met; pass only if within the FMO's failed-grid allowance
[Verify]. Two fail (18/20=90%) → Fail. - Any critical-area grid fails? → Fail (need ≥99%).
- Edition in force unknown? → treat affected citation as
[Verify], confirm with FM, don't pass on assumption. - Existing building found deficient on a periodic test? → §510.2 path → plan review.
- ERCES fault doesn't annunciate at FACP? → Fail the interface (510.4.2.5; see
../10-code/fire-alarm-and-erces.md). - Standby runs short of the required hours? → Fail; confirm FMO hours (12 vs 24
[Verify]). - Equipment not UL 2524 listed? → Fail (§18.12).
- Annual: >~3 dB drop vs baseline
[Verify]? → investigate / possible re-commission.
First Weeks
First Weeks
Days 1–3 — pin the foundations (clears P0 in OPEN-ITEMS)
- Confirm editions enforced: IFC, NFPA 1225 (2022 vs 2025), NFPA 72 — ask the FM.
- Confirm ERCES standby hours (12 vs 24) and the signal level (−95 dBm or FMO-set).
- Get FMO submittal forms, the Letter of Certification/Authorization process, fees, timelines.
- Get the radio-shop / SEGARRN POC and who signs FCC licensee consent.
- Read
../OPEN-ITEMS.mdtop to bottom; fold answers into the files + log in../CHANGELOG.md.
Week 1 — get current
- Shadow a plan review and an acceptance/annual test with the FM.
- Learn the grid test hands-on (
../40-field-test/grid-method.md); verify your instrument's cal (NIST ≤12 mo). - Walk a building's BDA/DAS + FACP interface end to end.
Weeks 2–4 — run it
- Lead a plan review using
../templates/plan-review-checklist.md. - Run an acceptance test with
../templates/field-test-datasheet.md+../templates/master-inspection-checklist.md; upload a completed checklist for analysis. - Each FM ruling → update the relevant file and
../CHANGELOG.md(date + who).
SEGARRN & Local
SEGARRN & Local Jurisdiction
Radio system
[Fact]SEGARRN — Southeast Georgia Regional Radio Network: a P25 trunked public-safety system, 700/800 MHz, serving Savannah/Chatham. The ERCES must rebroadcast its assigned channels.[Verify]Channels/talkgroups/control channels/donor site — operational data from the system manager / city radio shop (not public). Get the FCC licensee consent signer here. →../00-quickref/frequencies.md.
Georgia adoption
[Fact]2024 IFC is the Georgia statewide edition, effective 2026-01-01; the GA Safety Fire Commissioner (OCI) adopts/amends the IFC for fire enforcement (binds you), separate from DCA's base I-Codes.[Verify]Which NFPA 1225 (2022/2025) and NFPA 72 editions Georgia references.
Savannah/Chatham quirks
[Fact]The City's published BDA/ERRCS guide is 2018-IFC-based — map its citations to the in-force edition (../10-code/edition-deltas.md).[Verify]Savannah local amendments to §510 (signal level, standby hours, grid/failed-grid rule, donor-antenna gain cap, Class A requirement).[Verify]Chatham County (unincorporated) ERCES process — see../00-quickref/contacts.md.
Sources: ICC – Georgia · GA OCI
Glossary
Glossary
- ERCES — Emergency Responder Communication Enhancement System (2024 IFC term). The in-building system that makes responder radios work inside a building.
- ERRC — older term (2018 IFC), "Emergency Responder Radio Coverage." Same idea, renamed to ERCES.
- BDA — Bi-Directional Amplifier. Boosts the signal both ways (in and out).
- DAS — Distributed Antenna System. The network of indoor antennas the BDA feeds.
- Donor antenna — the (usually directional) outdoor antenna aimed at the public-safety tower; the BDA's link to the outside.
- Indoor / server antenna — the antennas inside the building that re-radiate the signal.
- DAQ — Delivered Audio Quality, 1–5 scale of voice intelligibility. 3.0 is the ERCES minimum.
- RSSI — Received Signal Strength Indicator (raw power, dBm). Coverage uses a level like −95 dBm.
- SINR / BER — Signal-to-Interference-plus-Noise Ratio / Bit Error Rate; P25 equivalents to DAQ 3.0 (~SINR ≥18 dB, BER ≤2.5%).
- P25 — Project 25, the digital public-safety radio standard SEGARRN uses.
- Trunking — many users sharing channels dynamically (vs fixed channels).
- Simulcast — multiple sites transmitting the same signal on the same frequency in sync.
- Isolation — RF separation between donor and indoor antennas; must be ≥ system gain + 20 dB.
- Oscillation — feedback when isolation is too low; the BDA amplifies its own signal.
- Desensitization (desense) — booster noise raising a receiver's noise floor, shrinking coverage.
- Near-far — strong nearby signal overwhelming a weak far one at an antenna.
- Link budget — the gain/loss accounting that predicts in-building signal.
- Class A / Class B — channelized (narrow) vs broadband BDA (FCC §90.219).
- UL 2524 — the listing standard for in-building 2-way ERCES equipment.
- UL 2196 / CI cable — 2-hour fire-rated circuit-integrity cable for survivable pathways.
- FACP — Fire Alarm Control Panel; where ERCES faults annunciate.
- AHJ — Authority Having Jurisdiction (here, the Savannah Fire Marshal).
- GROL — FCC General Radiotelephone Operator License (designer/installer qual).
- NEMA 4 / 4X — enclosure ratings (4X = corrosion-resistant).
- SEGARRN — Southeast Georgia Regional Radio Network (the local P25 system).
Open Items (verify w/ FM)
Open Items — Verify with the Fire Marshal
Rule: never present any of these as settled. When the FM rules, edit the affected file AND log it in
CHANGELOG.md(date + who said it), then check the box here.Ask:= who to confirm with.
P0 — foundational (everything keys off these)
- [ ] Adopted IFC edition in force, with local amendments. The City's published BDA/ERRCS guidance is 2018-based; GA's 2024 IFC is statewide effective 2026-01-01. Which governs a permit today, and what does Savannah amend in §510? — Ask: FMO. Blocks all citations.
- [ ] NFPA 1225 edition referenced (2022 vs 2025). 2025 adds explicit fire-alarm supervision interface. — Ask: FMO / GA OCI.
- [ ] Standby power: 12 hr vs 24 hr. IFC/NFPA baseline is commonly 12 hr; many AHJs require 24 hr by amendment. — Ask: FMO. Affects every battery calc.
- [ ] NFPA 72 edition adopted. Drives the monitoring/supervision + pathway requirements. — Ask: FMO.
P1 — thresholds & test method
- [ ] Exact signal threshold — is it −95 dBm, or an FMO-set level? And is DAQ 3.0 the adopted acceptance criterion or dBm-only? — Ask: FMO.
- [ ] Savannah grid method — confirm against the current City BDA doc: ≥20 grids/floor (20×20 ft; 40×40 if floor >32,000 sf) and the max # of failed common-area grids allowed. — Ask: FMO / savannahga.gov BDA doc.
- [ ] Baseline deviation that forces re-commissioning on annual test (e.g., >3 dB drop)? — Ask: FMO.
P2 — equipment & authorization
- [ ] Class A (channelized) required? Any donor-antenna gain cap (e.g., ≤10 dBi)? — Ask: FMO.
- [ ] Designer/lead-tech qualifications enforced (FCC GROL + approved training or mfr cert)? — Ask: FMO.
- [ ] Pathway survivability level required (2-hr CI cable everywhere vs conditioned)? Knox/access switch + signage specifics? — Ask: FMO.
P3 — SEGARRN / spectrum (radio shop)
- [ ] Licensee + who signs FCC §90.219 retransmit consent for SEGARRN. — Ask: Radio shop / SEGARRN manager.
- [ ] Channels / talkgroups / donor site / aiming for each building. — Ask: Radio shop.
- [ ] Acceptance-test radio (exact portable model/freqs) + whether the radio shop witnesses. — Ask: Radio shop / FMO.
P4 — process & contacts
- [ ] FMO direct line/email + ERCES submittal checklist/forms. — Ask: FMO.
- [ ] Letter of Certification (acceptance) and annual Letter of Authorization process, timeline, fees. — Ask: FMO.
- [ ] Retrofit / existing-building applicability + any phase-in. — Ask: FMO.
Resolved (move here with date + CHANGELOG entry)
(none yet)
Changelog
Changelog
Append-only. Each entry: date — who said it — what changed (and which file). Move resolved OPEN-ITEMS here.
2026-06-06 — initial build (Claude, from research; no seed handbook provided)
- Built Phases 0–5: scaffold, field cards, code core, operational sections, templates, decision trees, onboarding, jurisdiction, glossary.
- All claims researched + cited + certainty-labeled; no verbatim code text.
- No Fire Marshal rulings yet — every
[Verify]inOPEN-ITEMS.mdis still open. As the FM rules, log it here.